Receiving Helpdesk

what is a shared neutral in electrical terms

by Marcel Schuster Published 3 years ago Updated 3 years ago

What is a shared neutral in electrical terms? A shared neutral is a connection in which a plurality of circuits use the same neutral connection. This is also known as a common neutral, and the circuits and neutral together are sometimes referred to as an Edison circuit.

Shared neutral. A shared neutral is a connection in which a plurality of circuits use the same neutral connection. This is also known as a common neutral, and the circuits and neutral together are sometimes referred to as an Edison circuit.

Full Answer

What is a shared neutral?

 · A shared neutral is a connection in which a plurality of circuits use the same neutral connection. This is also known as a common neutral, and the circuits and neutral together are sometimes referred to as an Edison circuit.

What does Neutral Mean in electrical terms?

A multiwire branch circuit is a branch circuit with a shared neutral. This means there are two or more ungrounded (hot) phase or system conductors with a voltage between them and a shared neutral. Multiwire branch circuits are used in offices, hospitals, hotels, high-rise residential buildings, or similar facilities for a variety of power distribution systems including lighting, …

Can you share a neutral wire?

There is only one GFCI breaker in a shared neutral scenario. The sharing of the neutral is elsewhere beyond the circuit breaker panel, and the GFCI will not work as expected in this scheme. The GFCI works by measuring the current in both the hot and neutral wires. If they differ by more than 5 ma the breaker trips.

What happens when you disconnect a shared neutral?

 · One shared neutral is for all receptacles and the basement lights (two circuits). The other shared neutral is for the kitchen receptacle and the disposal (two circuits). All of the wiring is accessible (unfinished basemen...

How does a shared neutral work?

0:131:06Common or Shared Neutral - YouTubeYouTubeStart of suggested clipEnd of suggested clipSo each each breaker every other breaker is on is feeding from the left side and every other andMoreSo each each breaker every other breaker is on is feeding from the left side and every other and then the up that one's from the right side.

What does sharing a neutral mean?

A multiwire branch circuit is a branch circuit with a shared neutral. This means there are two or more ungrounded (hot) phase or system conductors with a voltage between them and a shared neutral.

How do you fix a shared neutral?

2:383:39SureTrace Shared Neutrals Video - YouTubeYouTubeStart of suggested clipEnd of suggested clipThen locate the shared neutrals in the electrical box and remove the wire connectors that splicingMoreThen locate the shared neutrals in the electrical box and remove the wire connectors that splicing them all together then separate and identify each circuits to neutral conductors.

Is it OK to share a neutral?

as long as the phase conductors are on different "phases" it's fine. Recent code requires them to be on a double pole breaker though. I do it as much as possible in houses. It's easier to pull one three wire for two circuits, than 2 separate two wires.

Can two lights share a neutral?

1 Answer. Show activity on this post. If not, no. If one circuit breaker turns off all three lights, then they are on the same circuit and you should be good to go.

How many receptacles can share a neutral?

You can only have one neutral per circuit in a single phase system, it is a current carrying conductor.

Can you tie neutrals together from different circuits?

As these joined neutrals include the travelers of both three-way circuits, the neutrals from the nearest light to each box, and the neutral heading back to the panel from each box, these two circuits' neutrals have multiple junction points that tie the neutrals together.

How do I find a shared neutral?

When the neutral is borrowed for the two way lighting in a domestic, you can see it by looking at the wiring of the upstairs 2 way switch; there will be two strappers from downstairs and a single switch line to the lighting point; no test required.

Can the neutral wire shock you?

Often, the neutral wire is very close to ground potential, and you are too. So, often, there is not enough voltage to give you a shock.

Can you put 2 neutral wires together in a breaker box?

Panel manufactures and the code The majority of the panel manufactures recommend only one neutral per slot. City building inspectors and home inspectors will normally call out this condition and recommend correction.Neutral Bar With Two Wires in One Hole - Buyers Askhttps://buyersask.com › electrical › electrical-panels › neut...https://buyersask.com › electrical › electrical-panels › neut...Search for: Can you put 2 neutral wires together in a breaker box?

Will an arc fault breaker work with a shared neutral?

Can the AFCI with shared neutral be used for retrofit installations? Yes, for retrofit installation, GE AFCIs can be substituted for the existing thermal magnetic breakers without the need to sort out existing shared or mixed neutrals.Arc Fault Circuit Interrupter (AFCI) with Shared Neutral FAQhttps://library.industrialsolutions.abb.com › DEQ-234https://library.industrialsolutions.abb.com › DEQ-234Search for: Will an arc fault breaker work with a shared neutral?

Will a GFCI work with a shared neutral?

You can't share the neutral on the output of the GFCI. It must only go to the outlets being protected. If you try to share this neutral your GFCI will not work and will trip immediately. Keep this neutral completely separate from other circuits.Can 2 gfci outlets share a neutral? - Sawmill Creek Woodworking ...https://sawmillcreek.org › showthread › 207880-Can-2-gf...https://sawmillcreek.org › showthread › 207880-Can-2-gf...Search for: Will a GFCI work with a shared neutral?

What happens when a current builds up on a neutral?

When a current builds up on the neutral, the neutral can overheat. The additional current will cause the problem to be compounded when multiple circuits are connected to the shared neutral and buildup will occur. This buildup damages the conductor, which will have adverse effects on equipment, degrade the quality of the power, and ultimately require replacement.

What is the purpose of a branch circuit with dedicated neutrals?

As an alternative, the use of individual branch circuits with dedicated neutrals for each ungrounded circuit conductor ensures that each circuit can be independently disconnected. A failure in one circuit will not adversely affect another.

What is the requirement for multiwire branch circuits?

What are the requirements for multiwire branch circuits? The National Electrical Code (NEC) mandates the simultaneous disconnect of multiwire branch circuits that supply electricity to more than one device on the same circuit. To be more specific, NEC® 210.4 (B) Disconnecting Means states, “Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates.”

Why is simultaneous disconnect dangerous?

The purpose of simultaneous disconnects – Multiwire branch circuits can be dangerous when all the ungrounded circuit conductors are not de-energized and the equipment supplied from a multiwire circuit is being worked on. Electricians run the risk of electrocution and injury while working on the equipment supplied by a multiwire branch circuit. The circuit can still be energized while work is being conducted or the proper protocol might not have been followed to disconnect the system. Simultaneous disconnects reduce the risk and takes the guess work out of ensuring safe conditions for maintenance.

Why is the electrical industry moving away from multiwire circuits?

Over the past decade, however, the electrical industry has been moving away from multiwire branch circuits to avoid the indiscriminate disconnection of power. It is simply not feasible for certain business operations to have an outage necessary for safe maintenance.

What is a multiwire circuit?

What is a multiwire branch circuit? A multiwire branch circuit is a branch circuit with a shared neutral. This means there are two or more ungrounded (hot) phase or system conductors with a voltage between them and a shared neutral.

How does a per phase cable mitigate harmonic distortion?

Neutral per phase cables can mitigate this harmonic distortion by reducing currents in the neutral conductor.

What happens if you share a neutral with two breakers?

If you were to share a neutral with two breakers on the same leg of a panel, both circuits could draw the breaker limit (lets say 15A) making the shared neutral as much as 30A return current! That will exceed the limit of the wire size and could cause a fire.

When did the code change for a shared neutral circuit?

The code requirement for the breaker to turn off both legs of shared neutral circuits is relatively new (after 1999). It is very likely that in older homes the circuit breakers for shared neutral circuits are not tied together and the user needs to turn off both breakers if he or she wants to avoid encountering current on the neutral wire. I encountered this issue in 1999 and asked my electrical inspector to submit this code requirement change. I'm a homeowner, not an electrician, but I have taken out electrical permits twice to wire additions to my homes.

How many circuits can you share in 3 phase?

You can share up to 3 circuits in 3 phase using 1 neutral but the 3 circuit breakers must be tied together with a breaker bridge so when 1 tries or 1 is turned off they all are off with no chance of getting bit by the neutral

How many 15 amps are in a multi wire circuit?

The result is that you get two 15amps circuits at one receptacle. At the panel, both breakers should be bonded together so it is not possible to have one on and one off.

Why should two breakers be ganged together?

The two breakers should be ganged together, so that if one trips, both will trip, and all junction boxes in the circuits become deenergized.

What happens when two separate supply lines share a neutral?

If two separate circuits fed from separate supply lines share a neutral, the main danger is when the neutral becomes disconnected. If this happens, voltage will dramatically increase on the circuits. The reason is the current will flow between the lines by going through whatever loads are connected.

Can you share a neutral?

Bottom line is you can share a neutral if the two hot wires are on different phases and the breakers are locked together

What is a tandem breaker?

A tandem breaker that fits into a single slot will have both of the tandem circuits on the same phase. A four breaker tandem (takes up two slots) will have the top two breakers on phase A and the bottom two on phase B. I often see these in use for multiwire circuits where the middle two breakers support one MW circuit and the outer two breakers supporting the other MW circuit.

Is all wiring accessible in basement?

All of the wiring is accessible (unfinished basement).

Does Eaton make a grounded breaker?

Yes…yet again Eaton does make a (2) pole “shared” grounded conductor AFCI breaker. But I am not sure if they are the only one that makes one.

Is it legal to have a shared neutral?

As Paul said, there is nothing wrong with them when they are installed properly. The shared neutral will not ever carry any more current than the load on either on the hot lines . It’s not the electricians I worry about. It’s what the homeowners do long after the electrican leaves - that’s what is realy scarry!

Is a shared neutral bad?

So, in this case, even with the tie in place, the circuit configuration would be unacceptable.

Can you use a shared neutral for AFCI?

You can use a shared neutral (with the hots from two different legs) for AFCI is you use a double pole AFCI circuit breaker (now available). Then you don’t have to pull a seperate neutral for each circuit.

Why do neutral wires have the same potential?

All neutral wires of the same earthed (grounded) electrical system should have the same electrical potential, because they are all connected through the system ground. Neutral conductors are usually insulated for the same voltage as the line conductors, with interesting exceptions.

Where are neutral wires connected?

Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are "bonded" to earth ground at either the electrical service entrance, or at transformers within the system. For electrical installations with split-phase (three-wire single-phase) service, the neutral point of the system is at the center-tap on ...

What is the IEC 60364?

The IEC standard ( IEC 60364) codifies methods of installing neutral and ground conductors in a building, where these earthing systems are designated with letter symbols. The letter symbols are common in countries using IEC standards, but North American practices rarely refer to the IEC symbols. The differences are that the conductors may be separate over their entire run from equipment to earth ground, or may be combined all or part of their length. Different systems are used to minimize the voltage difference between neutral and local earth ground. Current flowing in a grounding conductor will produce a voltage drop along the conductor, and grounding systems seek to ensure this voltage does not reach unsafe levels.

What is grounding in electrical?

Ground or earth in a mains ( AC power) electrical wiring system is a conductor that provides a low- impedance path to the earth to prevent hazardous voltages from appearing on equipment (high voltage spikes). The terms ground and earth are used synonymously in this section; ground is more common in North American English, and earth is more common in British English. Under normal conditions, a grounding conductor does not carry current. Grounding is also an integral path for home wiring because it causes circuit breakers to trip more quickly (ie, GFI ), which is safer. Adding new grounds requires a qualified electrician with knowledge particular to a power distribution region.

What is ground and neutral?

Ground and neutral are circuit conductors used in alternating current electrical systems. The ground circuit is connected to earth, and neutral circuit is usually connected to ground. As the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely related.

Where is the neutral in an AC system?

Neutral is usually connected to ground (earth) at the main electrical panel, street drop, or meter, and also at the final step-down transformer of the supply. That is for simple single panel installations; for multiple panels the situation is more complex. In a polyphase (usually three-phase) AC system, the neutral conductor is intended ...

Why is it important to connect a neutral to a case?

Connecting the neutral to the equipment case provides some protection against faults, but may produce a dangerous voltage on the case if the neutral connection is broken.

What is neutral wire?

In an electrical circuit, a neutral wire delivers the remaining power that was left after your smart switch or any kind of appliance draws current, back to the transformer outside your house. It is a path created to facilitate that residual current goes easily back to the energy company.

What is the extra neutral wire on a smart switch?

This extra neutral wire is connected to the Neutral bus and it will have constant current flowing through it. You don’t have it and you need to install it whether it’s you or a good electrician that actually knows what he’s doing.

How to check continuity of a wire?

If you are lucky enough to find the white cables twisted together covered with a plug you could do: 1 Remove the cover of the white cables 2 Put your multimeter to measure continuity. 3 First, identify the regular neutral wire using the images posted above. 4 Check for continuity of that cable all the way down until the neutral bus. 5 Once identified the neutral bus, check continuity between it, and the white cables twisted together in the back of your wall box. 6 If the multimeter is beeping, there you have it, that is your neutral wire.

Why do you need to connect a smart switch to a neutral wire?

Because the current takes the easiest path always and it will go back to the transformer. So, if you want to connect your smart switch to your neutral wire, sadly you’re going to need to install a third wire that is fed with electricity.

Why isn't my neutral wire energized?

The neutral wire that is inside your wall box is not energized because it is a dead-end for electricity. You won’t have energy flowing through it unless the switch closes the circuit and sends the remaining current back to the source.

Why is the neutral bus oscillating?

Keep in mind that the bus you are looking for is the one that is sending electricity back to the transformer! It should be oscillating because it depends on how much current is being drawn from your connected devices. It will vary, but if it’s showing you information, that’s your neutral bus.

What color wires are used for neutral?

Color cables: In a standard fairly new house, the color used for hot wires is white, which is the color used for neutral wires. At Least in the U.S. but it varies depending on the state you’re living, and that’s one of the biggest reasons are so easily confused.

What is the difference between dedicated and separate circuits?

A dedicated vs separate circuit is the argument-- As I seeit a dedicated circuit should not share a neutral and a separate circuit may share it. Others may disagree.

What is the intent of individual branch circuits?

However, I believe the intent of individual branch circuit is to limit conductors to not being shared by any other load.

What is a dedicated circuit?

IMO, dedicated circuit means it only powers a single piece of utilization equipment. Wiring can be either individual branch circuit or as part of a multiwire branch circuit. So my answer to the OP is, the neutral conductor can be either shared or not.

How many circuits are there in a 4 wire MWBC?

I agree. A 4 wire (A,B,C,N) MWBC from a 3?, Wye system would be 3 circuits. In some cases it can be considered one circuit, like in 225.30.

Can a neutral be shared?

Of course-- it couldn't be that easy that we would all agree. I see dedicate as both conductors having to be dedicated . If the neutral is shared then it is not dedicated to the circuit that requires it as dedicated. Whereas a separate circuit does not imply to me that the neutral cannot be shared. I can see it both ways but I see it clearer my way.

Is a dedicated circuit a branch circuit?

From this perspective, a dedicated circuit is essentially an individual branch circuit and vice versa.

Can a MWBC be both an individual branch circuit and a MWBC?

Since a MWBC must necessarily supply more than one utilization equipment, a circuit cannot be both an individual branch circuit and a MWBC.

image
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9