Would it be acceptable to use a 30mA sensitivity GFCI breaker?

Would it be acceptable by NEC to use a 30mA sensitivity (equipment protection) GFCI breaker for this food warming equipment? Thanks, and have a great day! GFCI protects people, GFP protetcs equipment. GFP is not acceptable whwere GFCI is required. By the NEC, no. NEC requires 5ma protection.

Do you have a GFI breaker on your 5 Ma breaker?

We've got a fair amount that has never had a GFI breaker on it, some with 5 mA breakers and the rest (obviously) is on 33 mA Breakers. I don't know that the 5 mA trips any more often than any other.

What does 30mA mean on a circuit breaker?

This means that a 30mA device can be used (IIRC this is class E protection). Old parallel CH BR afci breakers were clearly labeled on the side as having 30ma ground fault protection. That is the only time I have ever willingly installed an arc fault breaker.

What is a gfpe receptacle?

I am assuming you mean GFPE (30 milliamp trip threshold). GFPE is not used for kitchen equipment but is commonly used to protect roof de-icing cable. If it is not used for Commercial kitchen equipment, we are not talking about the same thing. I am not sure that there is any GFPE type of receptacles.

What is a GFPE breaker?

Ground-fault protection of equipment (GFPE) is defined in the National Electrical Code (NEC) [1] in Article 100 as “a system intended to provide protection of equipment from damaging line-to-ground-fault currents by operating to cause a disconnecting means to open all ungrounded conductors of the faulted circuit.

What does GFPE stand for?

Ground fault protection equipmentGround fault protection equipment (GFPE) can either consist of an equipment leakage current interrupter (ELCI) or ground fault sensing and relaying equipment. An ELCI is a device intended to provide leakage current protection in electrical appliances and electrical utilization equipment.

What milliamps does a GFCI trip at?

It takes only 5 mA (0.005 A) of current leakage from the hot wire to the ground to cause a GFCI to trip. A small amount of leakage current may be difficult to avoid in some normal circuits. Hand-held power tools do not cause a tripping problem if the tool is maintained in good condition.

What is the difference between GFP and GFCI?

In the NEC's Wiring and Protection Chapter, the NEC requires two types of ground fault protection: personnel protection and equipment protection. The former is known as Ground Fault Circuit Interrupter (GFCI) and the latter is known as Ground Fault Protection of Electrical Equipment (GFP).

What is the difference between GFCI and GFPE?

There are two types of ground-fault protection required by the NEC: 1) the GFCI and 2) the GFPE. A GFCI is intended to protect persons against shock and electrocution. As implied by its name, the GFPE protects equipment from damaging line-to-ground faults and is not intended for the protection of people.

Which of the following services requires that a GFPE device be installed?

GFPE is generally required for solidly grounded wye services and feeders of more than 150V to ground but not exceeding 600V phase-to-phase for each disconnect rated at or above 1,000 amperes (A). GFPE is required for nominal 480Y/277V, three-phase, 4-wire, wye-connected systems.

What is a 30mA GFCI?

Equipment Protection Ground-Fault Interrupters (30mA) Ground fault interrupters are an effective means of preventing severe electrical shock. A GFI device which protects equipment (not people) is allowed to trip as high as 30 mA of current.

Is there a difference between GFI and GFCI?

Ground fault circuit interrupters (GFCI) and ground fault interrupters (GFI) are the exact same device under slightly different names. Though GFCI is more commonly used than GFI, the terms are interchangeable.

What are the 3 types of GFCI?

Three types of GFCIs are commonly used in homes – the GFCI outlet, the GFI circuit breaker and the portable GFCI. All of these GFCIs perform the same function but each has different applications and limitations.

What is a GFP breaker?

Multi 9 GFP Ground Fault Protectors UL 1053 residual current circuit breakers already protected upstream by a short circuit and overload protection device are used for: control and disconnection of electric circuits. protection of people against electric shock by direct and indirect contacts.

Can I use AFCI instead of GFCI?

Yes, they both can be used on the same circuit; however, the Dual Function AFCI/GFCI Receptacle offers the option of providing both AFCI and GFCI protection in a single device.

Do they make a 30mA GFCI receptacle?

In the USA, the operating threshold for a GFCI for personal shock protection is 6mA. In most of the rest of the world, the threshold is 30mA.

What tool do you need to read milliamps?

The tool you need is a peak reading clamp meter or an oscilloscope with a current probe that can reliably read in the milliamp range. My experience is more in the lab, not in the field, so I don't know who near you would do this sort of work, or what equipment to recommend.

Does NEC require 5MA?

By the NEC, no. NEC requires 5ma protection.

Do GFI receptacles leak?

The GFI circuit breakers or GFI receptacles would not sense that their output and return had a leakage since they would be monitoring the difference in the potential of the phases or phase to neutral conductors associated with what was connected to them.

Does a 5mA GFCI need a NEC?

Thank you! Yes, it needs GF CI per NEC. So I have to talk to the GFCI manufacturer which 5mA GFCI trips a little bit more slowly, correct?

Special offers and product promotions

Amazon Business: Make the most of your Amazon Business account with exclusive tools and savings. Login now

Have a question?

There was a problem completing your request. Please try your search again later.

Product description

Manufactured by cutler hammer. Type ch ground fault equipment protector; 2-pole; 30 amp; 10 kaic; 120/240 vac

How many GFI breakers are there in a heat trace?

Just about every heat trace I've installed has 30 ma GFI breakers. Very rarely do they trip, if they do, there's usually a problem somewhere.

Does a 5 mA breaker trip?

We've got a fair amount that has never had a GFI breaker on it, some with 5 mA breakers and the rest (obviously) is on 33 mA Breakers. I don't know that the 5 mA trips any more often than any other. Typically, when there is a fault it will trip the breaker regardless of the GFI rating. If there is only a bit of moisture in an end or power kit, that might make a difference.

Do CH BR breaker have ground fault protection?

Old parallel CH BR afci breakers were clearly labeled on the side as having 30ma ground fault protection. That is the only time I have ever willingly installed an arc fault breaker. Gfpe breaker for a third of the cost :thumbup: :thumbup:

What is a Class B GFCI?

A Class B GFCI with a 20 milliamp trip level is to be used only for protection of underwater swimming pool lighting fixtures installed before adoption of the 1965 National Electrical Code (NEC).

What is a GFCI circuit?

The basic definition of a ground-fault circuit-interrupter (G FCI) is a general-use device whose function is to interrupt the electric circuit to a load within an established period of time. There is a Class A GFCI that trips when a ground fault current exceeds 5 milliamps and there is a Class B GFCI that trips when a ground fault current exceeds 20 ...

What is ground fault protection?

The most important thing to understand about ground fault protection devices is that one type is to protect personnel and the other is to protect electrical equipment, the latter having different trip levels for different types of protection. Three basic ground fault systems or leakage current protection devices are used in ...

Why would a 250V GFCI breaker trip?

Using a two pole 250v GFCI breaker for 125v loads may cause the breaker to trip since it senses an impalance of the load.

How many prongs are in a trace cable?

These trace cables come with 36" of slack cord to standard 3 prong 120 v that need to plug into something. However, the engineer is telling me the GFCI might be too sensative and to use GFEP. His words exactly " I have had installs with GFCIs, but that is not the most ideal way to install SR cable. "

How do I wire a 120V heater?

These are 120V heaters. You should use a 2 pole 15A breaker and run a 3 wire MWBC to two GFCI outlets under the roof soffit. You don't need to add currents together since each heater cable will be on a different phase in the MWBC. You can decide if you want a GFEP or not. I would try a regular 2 pole breaker and install two gfci plugs in soffit of roof next to where heater runs begin. If you get nuisance tripping replace the gfci plugs with regular duplex and spring for the $150 2 pole 15A GFEP breaker. Since the heaters are on a shingled wood framed roof there isn't a good path to ground so nuisance tripping might be unlikely with GFCIs. You don't need 10 awg wire either, 14-3 should be fine.

Why doesn't a GFCI trip?

I would imagine it's due to the properties of heat trace cable. As the cable heats up it's resistance would increase resulting in a loss big enough to trip a G FCI.

Can you hardwire a GFI cable?

Check with the manufacturer to see if the cables could be hardwired. If they can, you can eliminate the GFI protection.

Do GFEP breakers have neutrals?

GFEP breakers do have a neutrals as well.