by Brent Wyman Published 3 years ago Updated 3 years ago

Gfci is for people protection (5 ma) and gfpe is for equipment protection (30 ma). Had a conversation here recently with a guy that claimed that some electricians were allowed to SWITCH the gfci (5 ma) breaker for the gfpe (30 ma) breaker in a kitchen because the (NEW)freezers and refrigerators were tripping them.

Full Answer

What is the difference between GFCI and gfpe?

Ground fault protection - GFCI or GFPE - there is a difference Abstract: A ground-fault circuit-interrupter (GFCI) is an electrical device, either a receptacle or circuit breaker, which is designed to protect people from electric shock. GFCI protection should not be confused with ground-fault protection for equipment or grounding in general.

What is the difference between GFCI and AFCI protection?

Either GFCI or AFCI protection could save your home—or even your life or that of a loved one. GFCI stands for ground-fault circuit interrupter, and an AFCI is an arc-fault circuit interrupter. These devices prevent electrical shock, injury, and property damage.

What is the difference between a GFI and GFCI breaker?

This would be a GFCI breaker on your electric distribution panel and will protect multiple outlets. A GFI is a local Ground Fault Interrupter, it is at the outlet and not on the panel. So the slight difference here is whether you have protection over several outlets, that you reset at your panel, or single protection that you reset at the outlet.

What is the exception to the GFCI rule?

Exception No. 1 to (3) and (4): Receptacles that are not readily accessible and are supplied from a dedicated branch circuit for electric snow-melting or deicing equipment shall be permitted to be installed without GFCI protection. Your installation may qualify for this exception to 210.8 (B) (4)....

What is a GFEP breaker?

What is a ground fault equipment protector (GFEP) and why is it necessary? • A ground fault equipment protector is a device intended to provide protection of equipment against damaging line-to-ground currents by disconnecting all ungrounded conductors of the faulted circuit.

Is there a difference between GFCI and GFI?

Ground fault circuit interrupters (GFCI) and ground fault interrupters (GFI) are the exact same device under slightly different names. Though GFCI is more commonly used than GFI, the terms are interchangeable.

What's the difference between GFCI and GFPE?

A GFCI is intended to protect persons against shock and electrocution. As implied by its name, the GFPE protects equipment from damaging line-to-ground faults and is not intended for the protection of people.

Can you plug heat trace into a GFCI?

The installation instructions for constant wattage heat cable state that it must be plugged into a GFCI protected outlet. This kind of cable does not have the same electrical draw as self-regulating cable, and it is not really considered heavy electrical equipment.

What are the 3 types of GFCI?

Three types of GFCIs are commonly used in homes – the GFCI outlet, the GFI circuit breaker and the portable GFCI. All of these GFCIs perform the same function but each has different applications and limitations.

What are the 5 types of GFCI?

15 Amp Duplex Receptacle. Formerly known as the standard electrical outlet in American homes. ... Basic GFCI. GFCI's or ground fault circuit interrupters monitor the current flowing through the conductor to determine if any current is leaking from the circuit. ... Tamper Resistant GFCI. ... Weather Resistant GFCI. ... Self-Testing GFCI.

What is the purpose of GFPE?

Ground-fault protection of equipment (GFPE) provides protection from devastating arcing events and destructive arcing burn-downs. National Electrical Code (NEC) sections 215.10, 230.95, 240.13 and 517.17 provide GFPE requirements, and Article 100 defines it. Electric arcs generate significant amounts of heat.

What does GFPE stand for?

Ground fault protection equipmentGround fault protection equipment (GFPE) can either consist of an equipment leakage current interrupter (ELCI) or ground fault sensing and relaying equipment. An ELCI is a device intended to provide leakage current protection in electrical appliances and electrical utilization equipment.

Does heat trace need to be on a GFCI breaker?

The NEC requires all heat tracing to be protected against ground faults with a couple of exceptions noted in Sec. 427.22. There is big a difference between the ground-fault circuit interrupters (GFCIs) that are used for personnel and equipment protection.

Does heat trace need to be grounded?

N.E.C. 427-22 requires the use of Ground Fault Equipment Protection Devices on electrical heat trace cable systems. Effective July 1, 1996, all heat trace circuits are required to have GFEPD 30 mA protection.

Can heat tape cause a fire?

Sadly, heat tape has the potential to cause fires in homes and businesses. Many of these products consist only of non-regulating tape which plugs into a wall outlet. If the heat tape remains activated for long periods of time – especially if temperatures rise and/or the tape is well-insulated – it can spark a fire.

Is heat tape safe for PVC pipes?

If your building plumbing pipes are plastic, such as PVC water piping, use only pipe heat tape that has an automatic thermostat to control the heat tape temperature. Otherwise a very hot heating tape may damage the piping or even cause a leak.

What is a GFCI circuit?

The basic definition of a ground-fault circuit-interrupter (G FCI) is a general-use device whose function is to interrupt the electric circuit to a load within an established period of time. There is a Class A GFCI that trips when a ground fault current exceeds 5 milliamps and there is a Class B GFCI that trips when a ground fault current exceeds 20 ...

What is a Class B GFCI?

A Class B GFCI with a 20 milliamp trip level is to be used only for protection of underwater swimming pool lighting fixtures installed before adoption of the 1965 National Electrical Code (NEC).

What is ground fault protection?

The most important thing to understand about ground fault protection devices is that one type is to protect personnel and the other is to protect electrical equipment, the latter having different trip levels for different types of protection. Three basic ground fault systems or leakage current protection devices are used in ...

What is GFCI protection?

Abstract: A ground-fault circuit-interrupter (GFCI) is an electrical device, either a receptacle or circuit breaker, which is designed to protect people from electric shock. GFCI protection should not be confused with ground-fault protection for equipment or grounding in general.

What is GFPE in electrical?

Ground-fault protection of equipment (GFPE) is defined in the National Electrical Code (NEC) [1] in Article 100 as “a system intended to provide protection of equipment from damaging line-to-ground-fault currents by operating to cause a disconnecting means to open all ungrounded conductors of the faulted circuit.

How many amps can a GFPE hold?

A GFPE can be set up to 1,200 amperes with a time delay up to 1 second for ground-fault currents of 3,000 amperes or greater, which would be lethal to a human being. Published in: 2013 IEEE IAS Electrical Safety Workshop. Article #:

Is GFCI a fault?

GFCI protection should not be confused with ground-fault protection for equipment or grounding in general . Even if a system is properly grounded, minor faults in a circuit can cause a dangerous shock to a person using an appliance or power tool.

What is a GFCi breaker?

Gfci is for people protection (5 ma) and gfpe is for equipment protection (30 ma). Had a conversation here recently with a guy that claimed that some electricians were allowed to SWITCH the gfci (5 ma) breaker for the gfpe (30 ma) breaker in a kitchen because the (NEW)freezers and refrigerators were tripping them.

What is GFPE used for?

GFPE is not used for kitchen equipment but is commonly used to protect roof de-icing cable. If it is not used for Commercial kitchen equipment, we are not talking about the same thing. I am not sure that there is any GFPE type of receptacles. Our units are 120V and come with a cord and plug standard 5-15P.

What is the NEC code for ground fault protection?

210.8 (B) (2) requires all 125 volt 15 and 20 amp receptacles to have ground fault protection for personnel, which is defined in the NEC as a Class A device with a trip threshold of 4 to 6 milliamps. If the inspector was to approve GFPE protection which has a trip threshold of 30 to 50 milliamps IMHO that would constitute negligence on his part.

Why do commercial kitchens have GFCI protection?

The reason for GFCI protection in a commercial kitchen has to do with the wash down procedures and the fact that we are dealing with very conductive surfaces. The substantiation was a case where a janitor was mopping down the area in a commercial kitchen and touched a stainless steel appliance. The appliance had a broken ground prong on the cord and the motor in the appliance had faulted out to the frame. The janitor touched the appliance and was killed.

Is GFCi a 5 or 30 ma?

That gfci is a '5 ma' not the '30 ma' . They only say this is for equipment and the people won't be using that outlet much and that section was meant for outlets people can use frequently. Also, there is no 'specific statement in the code that says what the 'ma' should be' in that section, only that gfci is required.

Can an indicator light replace GFCI?

Most of the times the loss of the equipment grounding conductor occurs in the equipment plugged into the receptacle so an indicator light on the receptacle would not accomplish much in the way of safety and would never replace the safety provided by GFCI protection.

How to test a GFCI?

A: Testing a GFCI outlet is easy and should be done regularly. Start by plugging a light into the outlet and switch it on. Press the “TEST” button on the outlet (or distribution panel). You should see the reset button move to the outer position and the light will go out. This means the GFCI is working properly and you’ll need to press the reset button to restore power. If the light remains on, the GFCI protector needs to be replaced.

How to test GFCI circuit?

You can test the circuit by plugging a light into the outlet. If the light works and the circuit does not trip, you know that the GFCI and internal wiring is fine. This means that there is problem with one of the appliances plugged into that circuit. You will need to test all appliances one by one.

What happens when you press the test button on a GFCI breaker?

The user is protected by an insulted test button. When the test button is pressed, the GFCI breaker should open immediately. In other words, the GFCI will trip. Testing should be conducted regularly and the GFI outlet or GFCI breaker should be replaced if it is not functioning correctly.

How sensitive is a GFCI beaker?

They are incredibly sensitive, detecting around 4 – 5 milliamps electric loss.

How fast does a GFCI breaker shut off?

GFCI / GFI : A circuit breaker that quickly shuts off the flow of electricity (via relay) at a speed between 25–40 milliseconds, when it detects a difference (as small as 4 milliamps) between the electric current exiting the system compared to the current entering.

What is a GFCI breaker?

Technically, GFCI refers to a breaker that protects an entire circuit. This would be a GFCI breaker on your electric distribution panel and will protect multiple outlets. A GFI is a local Ground Fault Interrupter, it is at the outlet and not on the panel. So the slight difference here is whether you have protection over several outlets, ...

How long do GFCI circuit breaker batteries last?

However, any GFCI protector has a limited lifespan. Generally, these devices should last 10 – 20 years but they can fail in as little as 5 years. It is important to determine whether the CFCI device is tripping because of a ground fault, or a malfunctioning GFCI.

What is an AFCI circuit?

AFCIs, AFCI receptacles, and AFCI circuit breakers are designed to protect people and property from the dangers of an arc fault. If your home has them and they’re up-to-date, AFCIs will trip a circuit if a spark forms along faulty wiring.

What is AFCI protection?

GFCI stands for ground-fault circuit interrupter, and an AFCI is an arc-fault circuit interrupter. These devices prevent electrical shock, injury, ...

When did NEC start requiring AFCI protection?

And since AFCIs shut down an electrical system before a fire can start, the NEC began requiring their protection beginning in 1999. It has required AFCI protection for all bedroom wiring since 2002. In 2005, the NEC was expanded to include AFCIs combined with GFCIs, to reflect new and improved technologies.

What is cord AFCI?

A cord AFCI is like a portable AFCI, but it can be incorporated into a device or appliance’s permanent power cord. Therefore, when plugged into an electrical outlet, the connected apparatus is protected from arc faults.

Is an AFCI breaker a receptacle?

With today’s technology, an AFCI circuit breaker is strongly preferred over an AFCI receptacle. An AFCI circuit breaker covers the receptacle as well as the circuit leading to the breaker. AFCI circuit breakers are tested and certified rigorously to meet U.S. product safety standards.

Can I plug an AFCI into an outlet?

You can plug portable AFCI devices into conventional electrical outlets. They also provide one or more outlets for additional devices. Contractors who use these can enjoy a greater degree of electrical safety when using power tools.

Can you have GFCI outlets in kitchens?

In fact, the most expeditious path to the ground—whether that be spilled water or a living being standing in it—can provide that pathway. It’s critical to have only GFCI-equipped electrical outlets in bathrooms, kitchens, or laundry rooms.