common 3 phase voltages

by Trent Carroll Published 3 years ago Updated 3 years ago

480V 3 Phase is the most common power system used in US industrial plants. American National Standards Institute (ANSI) classifies 208V, 240V and 480V 3 Phase power as low voltage power systems. Other ANSI voltage classifications are Medium, High, Extra High, and Ultra High Voltage that goes up to 1,100,000V.

A common supply voltage is 120V/208V 3 phase Wye configuration. 120 volts is measured from each phase to neutral (neutral is center-tapped) and 208 volts is measured phase to phase. Wye configuration is commonly used to supply 3 phase 4 wire service entrances, such as commercial buildings.Dec 1, 2020

Full Answer

How do you measure 3 phase voltages?

How do you measure 3 phase voltage with a multimeter? To test the incoming voltage, place one of the multimeter’s probes on L1 and the other on L2. Allow the multimeter to display the voltage and then repeat the tests while probing L1 and L3, then L2 and L3. If the transformer is working properly, the voltage readings should be the same after ...

What are the 3 phase voltages in the USA?

  • wye (Y) - wye (Y) is used for small current and high voltage.
  • Delta (Δ) - Delta (Δ) is used for large currents and low voltages.
  • Delta (Δ) - wye (Y) is used for step-up transformers i.e., at generating stations.
  • wye (Y) - Delta (Δ) is used for step-down transformers i.e., at the end of the transmission.

How much voltage is 3 phase?

The voltage betwee two line is called line voltage . 3 phase system is expressed with line voltages. The line votage is 440 volt. Also the voltage between any one phase and neutral for a 3 phase system is 240 volts. How do I know if I have 3 phase power?

How to measure or check for 3 phase voltage?

Three-Phase V-I Measurement

  • Ports. The three measured phase-to-ground or phase-to-phase voltages. The Vabc output disappears when the Use a label parameter is selected or when the Voltage measurement menu is set to no.
  • Parameters. Select no if you do not want to measure three-phase voltage. ...
  • Model Examples
  • Extended Capabilities. Generate C and C++ code using Simulink® Coder™.
  • See Also

Is 3 phase always 400V?

In Three Phase System, the voltage level between any two phases out of three phases is 400V, Not 415, 440, 660 or 690V. This is only possible in case of ±% variation e.g. 400V±10% = 400V + 40V = 440V.

How many 3 phase voltages are there?

Three Phase Three Wire Delta Nominal service voltages of 240, 400, 480, 600, and higher are typical.

Is 3 phase 400V or 415V?

For three-phase supplies the voltage was 415 V +/- 6%, the spread being from 390 V to 440V. Most continental voltage levels have been 220/380V.

Is 240V 3 phase common?

240V power is used in the US and parts of the world. In the US 120 / 240V 1 Phase 3 Wire is the standard for homes and 240V 3 Phase Open Delta is the standard for small buildings with large loads. In parts of the world 240V Single Phase 2 Wire is the standard for homes.

Is 3 phase 415V or 440V?

As shown in the figure below, the 3 phase supply has three wires (RYB). The voltage across any one phase and neutral is 220V, and the voltage across the 3 phase is 440V because we check the voltage between any two-phase RY or YB or BR.

What is the difference between 415V and 440V?

By motor you mean a 3-phase induction motor. If 440 V instead of 415 V is given, to develop a higher emf the flux will increase slightly (~ by a factor (440/415), thus increasing the magnetising current and hence iron loss.

Is 3 phase always 415V?

Having 3 phases allows us to have both 240V and 415V power from the same electricity supply.

Is UK a 400V or 415V?

The UK used 415VAC 50Hz. Currently, ALL Western European 3 phase supplies are classified 400VAC. In reality there is no 400VAC supply unless you create one locally. 400VAC was a “standard” created during European "harmonisation" to give a single voltage standard across Western Europe, including UK and Irish Republic.

Is 400V the same as 415V?

It may be that the manufacturer produces motors for 400V, 415V and 440V (the three common voltages in that region) and has a single production line for all three, in which case the motor will be exactly the same as a 415V motor.

Is all 208V 3 phase?

Conclusion. Now to get back to our question. 208 volts is Line-to-Line Voltage. This three Phase voltage is frequently used in small businesses.

What is the difference between 208V and 240V 3 phase?

They require two legs of power from the power utility, whereas 240v motors and appliances only use one. You will commonly see 208v present in three-phase buildings when “single-phase” equipment (like an A/C condenser) is wired to two legs of three-phase wye power.

Is 240V 3 phase the same as 208V 3 phase?

208V is *not* the same as 240V. 208V is the voltage between phases of a 3-phase “Y” circuit that is 120V from neutral to any hot. 480V is the voltage between phases of a 3-phase “Y” circuit that's 277V from hot to neutral.

What is three phase power?

Three-phase electric power is a common method of alternating current electric power generation, transmission, and distribution. It is a type of polyphase system and is the most common method used by electrical grids worldwide to transfer power.

How much power can a three phase AC supply transmit?

As compared to a single-phase AC power supply that uses two conductors (phase and neutral ), a three-phase supply with no neutral and the same phase-to-ground voltage and current capacity per phase can transmit three times as much power using just 1.5 times as many wires (i.e., three instead of two). Thus, the ratio of capacity to conductor material is doubled. The ratio of capacity to conductor material increases to 3:1 with an ungrounded three-phase and center-grounded single-phase system (or 2.25:1 if both employ grounds of the same gauge as the conductors).

Why do transformers change the voltage?

At the power station, transformers change the voltage from generators to a level suitable for transmission in order to minimize losses.

Why is a three phase circuit more economical than a two phase circuit?

A three-wire three-phase circuit is usually more economical than an equivalent two-wire single-phase circuit at the same line to ground voltage because it uses less conductor material to transmit a given amount of electrical power.

What is the order of the phase in a three phase system?

Normalized waveforms of the instantaneous voltages in a three-phase system in one cycle with time increasing to the right. The phase order is 1‑2‑3. This cycle repeats with the frequency of the power system. Ideally, each phase's voltage, current, and power is offset from the others’ by 120°.

What is a 4 wire wye?

The four-wire wye system is used when a mixture of single-phase and three-phase loads are to be served, such as mixed lighting and motor loads. An example of application is local distribution in Europe (and elsewhere), where each customer may be only fed from one phase and the neutral (which is common to the three phases). When a group of customers sharing the neutral draw unequal phase currents, the common neutral wire carries the currents resulting from these imbalances. Electrical engineers try to design the three-phase power system for any one location so that the power drawn from each of three phases is the same, as far as possible at that site. Electrical engineers also try to arrange the distribution network so the loads are balanced as much as possible, since the same principles that apply to individual premises also apply to the wide-scale distribution system power. Hence, every effort is made by supply authorities to distribute the power drawn on each of the three phases over a large number of premises so that, on average, as nearly as possible a balanced load is seen at the point of supply.

What is power transfer into a linear balanced load?

Power transfer into a linear balanced load is constant. In motor/generator applications, this helps to reduce vibrations.

What voltage is used for a 3 phase motor?

Nominal service voltages of 240, 400, 480, 600, and higher are typical.

How many times is line to line voltage in three phase systems?

Line-to-line voltages in three phase systems are typically 1.732 times the phase-to-neutral voltages:

What phase is a motor connected to?

Motors are connected to phase A, B, and C, while single-phase loads are connected to either phase A or C and to neutral. Phase B, the high or wild leg, is not used as the voltage to neutral is 208 volt.

What is the voltage of a Wye connected system?

Wye connected systems have a neutral. Delta connected systems typically do not have a neutral. Voltage classes: (ANSI C84.1-2016) Low Voltage: 1000 volts or less. Medium Voltage: greater than 1000 volts and less than 100 kV. High Voltage: greater than 100 kV and equal to or less than 230 kV.

What is the most common electrical service for commercial buildings?

The most common commercial building electric service in North America is 120/208 volt wye, which is used to power 120 volt plug loads, lighting, and smaller HVAC systems. In larger facilities the voltage is 277/480 volt and used to power single phase 277 volt lighting and larger HVAC loads. In western Canada 347/600V is common.

What are the two classes of voltages?

This ANSI standard describes two "classes" of voltages; "Distribution" and "Utilization".

What is the voltage of a transformer?

Here in the US, the transformer is normally rated higher than the motor (or load) to allow for voltage drops. The transformer secondary is usually 480 (or 240 or 208) and the motors are rated 460, 230 or 200 volts. 480 and 460 are considered the same. There are some industeries in the US that use 600 volts at transformer and 575 volt motors.

What is 208V for 240V?

Equipment is designed around the "Utilization Voltage" levels, so motors for example are designed to accept lower voltages, assuming that by the time the Distributed voltage gets to the motor terminals, it will be lower. So for example if a plant has 480V, the motors would be designed for 460V, +- 10%. So for 208V, that is 200V, for 240V it is 230V. Because of the preponderance of 208V systems, and the fact that MOST motors being used in these smaller installations would be smaller motors, many motor mfrs chose to reduce their inventory by marketing motors under 10HP as "208-230V". These are a compromise design that is based on a 220V criteria, +10, -15% (by incorporating a little more iron).

What is the standard voltage for a power line?

In My experience (16 years in industry) the standard is 480volts. I consider 460V to be the same and even 440V is within the 10% rule. With a good supply the voltage will stay between475V and 481V. In some areas you will find mucjh greater dips and sensitive equipment will need a constan voltage transformer. Many industrial settings also make extensive use of variable frequency drives which can generate alot of noise on power lines in the plant but that is another subject.

What voltage is used in the US?

I am less certain as to what is used in the US, but I believe that 480 and 440 are the most common, plus of course they also use 208 due to the relationship to 120. An American could probably give you a better idea of the correct proportions for the various voltages.

How many volts does a transformer use?

There are some industeries in the US that use 600 volts at transformer and 575 volt motors. The above covers most 3 phase usage in the US. There has been voltage creep over the years - in the 1930s and 40s (maybe even 50s)the transformers were rated 460 (or 230 volts) and the motors were rated 440 and 220 volts.

What voltage is light industrial?

Agreed, but don't forget "light industrial", those guys with the small shops and 208/120 volt systems.

What are the four major voltage classes?

The four major voltage classes are 5, 15, 25, and 35 kV. A voltage class is a term applied to a set of distribution voltages and the equipment common to them; it is not the actual system voltage.

What is the most common 15 kV voltage?

Utilities most widely use the 15-kV voltages as shown by the survey results of North American utilities in Figure 1. The most common 15-kV voltage is 12.47 kV, which has a line-to-ground voltage of 7.2 kV.

Why do higher voltages have more sags?

Higher voltage systems have more voltage sags because faults further from the substation can pull down the station’s voltage (on a higher voltage system the line impedance is lower relative to the source impedance). Cost comparison between circuits is difficult (see Table 2 for one utility’s cost comparison).

What are the advantages and disadvantages of higher voltage distribution?

The great advantage of higher voltage systems is that they carry more power for a given current.

Why is it important to have a higher voltage?

As far as ongoing maintenance, higher voltage systems require less substation maintenance, but higher voltage systems should have more tree trimming and inspections to maintain reliability. Conversion to a higher voltage is an option for providing additional capacity in an area. Conversion to higher voltages is most beneficial when substation space is hard to find and load growth is high.

How much area can a 24.94 kV system cover?

Area coverage – For the same load density, the area covered increases linearly with voltage: A 24.94-kV system can cover twice the area of a 12.47- kV system; a 34.5-kV system can cover 2.8 times the area of a 12.47-kV system. where: V1, V2 = voltage on circuits 1 and 2. P1, P2 = power on circuits 1 and 2.

What is the cost comparison between circuits?

Cost comparison between circuits is difficult (see Table 2 for one utility’s cost comparison). Higher voltage equipment costs more – cables, insulators, transformers, arresters, cutouts, and so on. But higher voltage circuits can use smaller conductors. The main savings of higher-voltage distribution is fewer substations.

Overview

Three-wire and four-wire circuits

There are two basic three-phase configurations: wye (Y) and delta (Δ). As shown in the diagram, a delta configuration requires only three wires for transmission but a wye (star) configuration may have a fourth wire. The fourth wire, if present, is provided as a neutral and is normally grounded. The three-wire and four-wire designations do not count the ground wire present above many transmission li…

Terminology

The conductors between a voltage source and a load are called lines, and the voltage between any two lines is called line voltage. The voltage measured between any line and neutral is called phase voltage. For example, for a 208/120 volt service, the line voltage is 208 Volts, and the phase voltage is 120 Volts.

History

Polyphase power systems were independently invented by Galileo Ferraris, Mikhail Dolivo-Dobrovolsky, Jonas Wenström, John Hopkinson, William Stanley Jr., and Nikola Tesla in the late 1880s.
Three phase power evolved out of electric motor development. In 1885, Galileo Ferraris was doing research on rotating magnetic fields. Ferraris experimented …

Principle

In a symmetric three-phase power supply system, three conductors each carry an alternating current of the same frequency and voltage amplitude relative to a common reference, but with a phase difference of one third of a cycle (i.e. 120 degrees out of phase) between each. The common reference is usually connected to ground and often to a current-carrying conductor called the neutr…

Advantages

As compared to a single-phase AC power supply that uses two conductors (phase and neutral), a three-phase supply with no neutral and the same phase-to-ground voltage and current capacity per phase can transmit three times as much power using just 1.5 times as many wires (i.e., three instead of two). Thus, the ratio of capacity to conductor material is doubled. The ratio of capacity to conductor material increases to 3:1 with an ungrounded three-phase and center-grounded sin…

Generation and distribution

At the power station, an electrical generator converts mechanical power into a set of three AC electric currents, one from each coil (or winding) of the generator. The windings are arranged such that the currents are at the same frequency but with the peaks and troughs of their wave forms offset to provide three complementary currents with a phase separation of one-third cycle (120° or 2…

Transformer connections

A "delta" connected transformer winding is connected between phases of a three-phase system. A "wye" transformer connects each winding from a phase wire to a common neutral point.
A single three-phase transformer can be used, or three single-phase transformers.
In an "open delta" or "V" system, only two transformers are used. A closed delta made of three single-phase transformers can operate as an open delta if one of the transformers has failed or …